We have a Honeywell controller on a Webster burner on our boiler.

Last Edit: January 26, 2023
Get Expert Help Now Get Expert Help Now
Oliver Maslou
Oliver Maslou Tech Expert & Writer
Hello, thank you for contacting Howly! I am here to help you today!
May I know your first name, please?
Customer Reply
*****
Oliver Maslou
Oliver Maslou Tech Expert & Writer
Nice to meet you, *****!
Customer Reply
I need to know the problems exposed when the Honeywell controller on our burner for the boiler blinksHoneywell
Oliver Maslou
Oliver Maslou Tech Expert & Writer
If you find that you keep having to reset your boiler, it's likely that there could be a fault with your heating system. This fault could eventually lead to a more serious issue such as a boiler breakdown, so it's best to seek out a solution as soon as possible.
Customer Reply
that is what I am trying to do. The steam boiler filled with water the other day, it shut down on high water as it should. This is fixed now and it seems to be working properly except the power light continues to blink instead of remain on. Is that a problem?
I know that when a certain blinking of the status lights occur, it tells you the problem. Where can I find the status of these blinking lights?
Oliver Maslou
Oliver Maslou Tech Expert & Writer
Got it!
Please allow me a moment to provide you with further instructions, I would really appreciate it if you would wait for me in the chat. Thank you!
If the batteries are dying, your thermostat could be blinking the “Cool On” message. When your thermostat doesn't have enough power, it won't be able to start the cooling or heating process. To properly check your batteries, look for the “Battery Low Indicator” message on the thermostat display.
Customer Reply
it is not the thermostat it is the controller for the burner on our boiler.
can I send you a picture?
Oliver Maslou
Oliver Maslou Tech Expert & Writer
Sure.
To attach pictures to our chat, you need to press the paper clip button in the lower right corner of the chat window. Then you have either to choose an image on your device or take a photo right away. Then confirm sending.
Customer Reply
Visitor uploaded:Image.jpeg
Oliver Maslou
Oliver Maslou Tech Expert & Writer
Thank you for the picture!
Customer Reply
In this case, you need to reset your Honeywell burner control. Please follow these instructions.
Press and hold the reset button for 30 seconds.
When the LED flashes once for one second, the device has reset.
The R7184 will enter the lockout mode when: Flame is detected during valve-on delay.
Please keep me posted.
Oliver Maslou
Oliver Maslou Tech Expert & Writer
thank you
Customer Reply
Let me know how everything is going.
Oliver Maslou
Oliver Maslou Tech Expert & Writer
it worked, thank you again!
Customer Reply
Do you have any additional questions I can help you with?
Oliver Maslou
Oliver Maslou Tech Expert & Writer
is there a Honeywell site I can go to to see the full instructions on this type of control?
Customer Reply
Please visit this link https://www.honeywellhome.com/us/en/support/
Here you can find detailed information regarding many issues with Honeywell.
If you have any other questions, I'll be happy to help you out!