Updated: March 20, 2023
125 Views
Was it helpful?
author
by Oliver Maslou
Tech Expert & Writer
849 resolved issues

We have a Honeywell controller on a Webster burner on our boiler.

author



Hello, thank you for contacting Howly! I am here to help you today!
May I know your first name, please?

Customer Replay


*****

author


Nice to meet you, *****!

Customer Replay


I need to know the problems exposed when the Honeywell controller on our burner for the boiler blinks

image

Customer Replay




If you find that you keep having to reset your boiler, it's likely that there could be a fault with your heating system. This fault could eventually lead to a more serious issue such as a boiler breakdown, so it's best to seek out a solution as soon as possible.

banner 3
author


that is what I am trying to do. The steam boiler filled with water the other day, it shut down on high water as it should. This is fixed now and it seems to be working properly except the power light continues to blink instead of remain on. Is that a problem?
I know that when a certain blinking of the status lights occur, it tells you the problem. Where can I find the status of these blinking lights?

Customer Replay


Got it!
Please allow me a moment to provide you with further instructions, I would really appreciate it if you would wait for me in the chat. Thank you!
If the batteries are dying, your thermostat could be blinking the “Cool On” message. When your thermostat doesn't have enough power, it won't be able to start the cooling or heating process. To properly check your batteries, look for the “Battery Low Indicator” message on the thermostat display.

author


it is not the thermostat it is the controller for the burner on our boiler.
can I send you a picture?

Customer Replay


Sure.
To attach pictures to our chat, you need to press the paper clip button in the lower right corner of the chat window. Then you have either to choose an image on your device or take a photo right away. Then confirm sending.

author


Visitor uploaded:Image.jpeg

Customer Replay


Thank you for the picture!

banner 6
author


In this case, you need to reset your Honeywell burner control. Please follow these instructions.
Press and hold the reset button for 30 seconds.
When the LED flashes once for one second, the device has reset.
The R7184 will enter the lockout mode when: Flame is detected during valve-on delay.
Please keep me posted.

Customer Replay


thank you

author


Let me know how everything is going.

Customer Replay


it worked, thank you again!

author


Do you have any additional questions I can help you with?

Customer Replay


is there a Honeywell site I can go to to see the full instructions on this type of control?

banner 9
author


Please visit this link

https://www.honeywellhome.com/us/en/support/


Here you can find detailed information regarding many issues with Honeywell.
If you have any other questions, I'll be happy to help you out!

https://imagedelivery.net/cT5c9Z7JJOphL0SI-n4Eyw/d8ede0e9-e300-418a-75e9-ec6f1955f100/width=80
Our expert Oliver is online and ready to resolve your issues
849 resolved issues
Share on:
Copy to clipbord
Was it helpful?

Get answers until you're satisfied

/images/experts/tech/DannisK.webp
/images/experts/tech/StacyS.webp
/images/experts/tech/BorisP.webp

14 verified experts are online now

Boris P.

Expert's Assistant

Boris P.
Ask your question here

No comments yet...

What about starting a discussion? Be the first to share your thoughts!

Write a comment

We use cookies to improve your browsing experience on our site, show personalized content and targeted ads, and analyze site traffic.
More info